Application of Fault Location Mode Based on Travelling Waves for Neutral Non-effective Grounding Systems

Tao Ji; Qian-qian Yuan; Chang-ming Li; Ying Sun


 Scientific Research Office Weifang University Weifang, China ;College of  Information and Electrical EngineeringShandong University of Science and Technology Qingdao, China


 
Abstract—Fault location for distribution feeders short circuit especially single-phase grounding fault is an important task in distribution system with non-effectively grounded neutral. Fault location mode for distribution feeders using fault generated current and voltage transient traveling waves was investigated. The characteristics of transient traveling waves resulted from each short circuit fault and their transmission disciplinarian in distribution feeders are analyzed. This paper proposed that double end travelling waves theory which measures arriving time of fault initiated surge at both ends of the monitored line is fit for distribution feeders but single end traveling waves theory not. According to different distribution feeders, on the basis of analyzing original traveling waves reflection rule in line terminal, Current-voltage mode, voltage-voltage mode and current-current mode for fault location based on traveling waves are proposed and aerial mode component of original traveling waves is used to realize fault location. Experimental test verify the feasibility and correctness of the proposed method.


Keywords—distribution feeders; neutral non-effective grounding; traveling waves; fault locationmode
 

Manuscript Number: 1674-8042(2010)supp.-0133-06
 

dio: 10.3969/j.issn1674-8042.2010.supp..37
 

References
 

[1] YANG Xue-chang ,WENG Yang-bo, WU Zhen-sheng, 2002 .Theoretical Analysis of Transfer Function Algorithm for Grounded Fault Location in Three Phase Power Distribution Lines, High Voltage Apparatus,12(8) :15-18.
[2] Ranjbar A M, Shirani A R , Fathi A F,1992. A new approach for fault location problem on power lines. IEEE Trans on Power Delivery, 1(7):146-151.
[3] LI Meng-qiu,WANG Yao-nan, WANG Hui , 2001. A New Approach on Detecting the Single-to Ground Fault Location on Power System with Neutral Unearthed.Proceedings of the CSEE, 10(21):6-9.
[4] SANG Zai-zhong,PAN Zhen-cun, LI Lei , 1997.A New Approach of Fault Line Identification, Fault Distance Measurement and Fault Location for Single Phase-to-Ground Fault in Small Current Neutral Grounding System.Power System Technology, 10(21):50-52.
[5] YAN Feng,YANG Qi-xun, QI Zheng , 2004.Study on Fault Location Scheme for Distribution Network Based on Travelling Wave Theory, Proceedings of the CSEE, 9(4):37-43.
[6] CAI Yu-mei,HE Zheng-you,and WANG Zhi-bing , 2005.pplication of Travelling Wave Based Fault Location in 10KV Railway Automatic Blocking and Continuous Power Transmission Lines, Power System Technology, 1(29):15-19.
[7] HE Jing-han,JI Ying-ye, 2004 .Research of Fault Distance Measure Algorithm for Non-Direct-Ground Neutral System, North China Electric Power, 1:1-3.
[8] XU Bing-yin, LI Jing, CHEN Ping , 2001.Modern Fault Location Techniques Based on Fault Generated Travelling Waves and Their Applications,Automation of Electric Power Systems, 23(25):62-65.
[9] Qin Jian, Chen Xiangxun, Zheng Jianchao , 2000.A new double terminal method of travelling wave fault location using wavelet transform, Proceedings of the CSEE, 8(20):6-10.
[10] GE Yao-zhong, 1996. New Types of Protective Relaying and Fault Location Theory and Techniques,Xi’an: Xi’an Jiaotong University Press
[11] DONG Xin-zhou, 1996.Application of Wavelet Transform to Transmission Line Fault Location, Doctoral Dissertation.,Xi’an: Xi’an Jiaotong University
[12] QIN Jian, CHEN Xiang-xun,  ZHENG Jian-chao, 1999.Study on Dispersion of Travelling Wave in Transmission Lion,Proceedings of the CSEE, 9(19):27-30.
 

 
[full text view]